ON-LINE ORDER
HOME PAGE
CONTACT US

1-800-843-6036

1-800-843-6036

 

 

Fire Alarm PVC Unshielded

fire alarm wire cable 14awg 14 awg gauge 2 c conductor wires cables

Fire Alarm PVC Unshielded

 

Fire Alarm PVC Shielded

shield shielded fire alarm wire cable wiring cables wires 16 awg gauge 2 c conductor

Fire Alarm PVC Shielded

 

Fire Alarm Plenum Rated Unshielded

nyc new york city approved plenum fire alarm wire cable unshielded fplp rated 14 awg 1 pair

Fire Alarm Plenum Rated Unshielded

 

Fire Alarm Plenum Rated Shielded

fire alarm plenum rated wire cable nyc new york city approved fplp shielded 16awg 16 awg 1 pair

Fire Alarm Plenum Rated Shielded

ON-LINE ORDER
HOME PAGE
CONTACT US

1-800-843-6036

 

 

EXPLOSION PROOF HEAT DETECTORS FOR INSTALLATION IN HAZARDOUS LOCATIONS

 

Model 302-epm explosion proof explosion-proof explosionproof heat detector detectors for hazardous locations

Explosion-Proof Heat Detectors

Must be hand tightened only.

Must be attached to explosion proof outlet body.

model 302-epm diagram

135°F  & 194°F Models

Detectors are not directionally effected, can be mounted horizontally or vertically.

ExplosionProof heat detector for installation in hazardous locations. Has hexagonal grip bushing with 1/2" conduit threads for attachment to threaded explosion proof outlet body with cover.

APPROVALS/LISTINGS:

  • UL Underwriters Laboratories

  • California State Fire Marshal Listing No. 7270-0021:001

  • MEA Acceptance# 193-03-E

General:

These explosion proof heat detectors are normally open devices designed especially for fire detection and alarm systems. These rate compensation type detectors are available in either 135 degree F or 194 degree F models. These explosion-proof heat detectors are self restoring, hermetically sealed, shock and corrosion resistant, and are tamper proof. Refer to NFPA Standard 72, Standard for automatic fire detectors for application requirements, testing and maintenance.

Principal of Operation:

These explosion proof heat detectors operate on the principles of a rate compensation detector. The heat detector consists of a high expansion aluminum tube which encases two insulation struts with opposing open constant points. The high expansion sensing shell and the expansion struts have a different coefficient of expansion. A slow rate of temperature rise allows the heat to penetrate the inner expansion struts. Therefore, the tubular shell and the struts expand slowly until the total device has been heated to its rated temperature level of 135 degree F. or 194 Degree F. At this point, the silver contact points close which initiates the alarm. When subjected to rapid rate temperature rise there is not as much time for heat to penetrate the inner strut. The rapid lengthening of the shell allows the struts to come together at a lower level which compensates for thermal lag inherent in conventional fixed temperature detectors. When the surrounding air temperatures go below the rated temperature level, the shell contracts which forces contacts to open, thus automatically resetting the detector.

PRICING:

MODEL# DESCRIPTION *WEB PRICE

1-3 UNIT PRICING

*WEB PRICE

4 OR MORE PRICING

302-EPM-135 135° EXPLOSION PROOF HEAT DETECTOR**DETECTOR ONLY** $98.99 EACH $79.99 EACH
302-EPM-194 194° EXPLOSION PROOF HEAT DETECTOR**DETECTOR ONLY** $98.99 EACH $79.99 EACH
302-EPM-135-K 135° EXPLOSION PROOF HEAT DETECTOR- COMPLETE- READY TO INSTALL WITH RECOMMENDED EXPLOSION PROOF  OUTLET BODY $259.99 EACH $219.00 EACH
302-EPM-194-K 194° EXPLOSION PROOF HEAT DETECTOR- COMPLETE- READY TO INSTALL WITH RECOMMENDED EXPLOSION PROOF  OUTLET BODY $259.99 EACH $219.00 EACH

1-800-843-6036

*PRICES SUBJECT TO CHANGE WITHOUT NOTICE.

INVENTORY SUBJECT TO PRIOR SALE.

NOT RESPONSIBLE FOR ERRORS IN PRINT.

Product Design & Specifications subject to change without notice.

© Copyright 2007 MidSouth Wire & Cable Co. All Rights Reserved.